Rated voltage (maximum) | 720 V |
Test voltage | 3 kV A.C. (1 min) |
Frequency | 50-60 Hz |
Rated short-time thermal current | Ith = 60 In for wound primary transformers Ith limited by cable sizes or primary bus-bar for other cases |
Rated dynamic current | Idyn = 2,5 x Ith |
Continuous overload | 1,2 x In |
Operating temperature | от -10 °C до +50 °C |
Cable | accuracy class 0,2, 0,2S и 0,5S по запросу |
Rated secondary current | /5 A or /1 A |
Insulation class | B (130º C) |
standarts | IEC 185 UNE EN 61869 VDE 0414 IEC 801/1-3.4 DIN 57414 BS 3938 EN 50081 EN 50082 IEC 1010 |
TA30P | TA60P | TA80P | TA100P | TA125P | TA160P | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Bus-bar | 30x20 | 60x30 | 80x50 | 100x80 | 125x80 | 160x80 | ||||||||||||
Cable | Ø20 | Ø30 | Ø50 | Ø80 | Ø80 | Ø80 | ||||||||||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | VA | VA | VA | VA | ||||||||||||
100 | 3 | |||||||||||||||||
150 | 3,75 | |||||||||||||||||
200 | 2,5 | 4 | ||||||||||||||||
250 | 3,75 | 5 | 2,5 | 3,75 | 2,5 | 3,75 | 2,5 | 3,75 | ||||||||||
300 | 2,5 | 4 | 6 | 3,75 | 5 | 3,75 | 5 | 3,75 | 5 | |||||||||
400 | 3,75 | 5 | 10 | 2,5 | 3,75 | 7,5 | 2,5 | 3,75 | 7,5 | 2,5 | 3,75 | 7,5 | ||||||
500 | 3,75 | 5 | 15 | 3,75 | 5 | 15 | 3,75 | 5 | 15 | 5 | 7,5 | 2,5 | 3,75 | 7,5 | ||||
600 | 5 | 7,5 | 20 | 5 | 7,5 | 20 | 5 | 7,5 | 20 | 5 | 15 | 3,75 | 5 | 10 | ||||
750 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 5 | 10 | 20 | 5 | 10 | 20 | |||
800 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | |||
1000 | 10 | 15 | 20 | 10 | 15 | 20 | 10 | 15 | 20 | 10 | 20 | 30 | 10 | 20 | 30 | |||
1200 | 15 | 20 | 30 | 15 | 20 | 30 | 15 | 20 | 30 | |||||||||
1500 | 15 | 20 | 30 | 20 | 30 | 45 | 20 | 30 | 45 | |||||||||
2000 | 20 | 30 | 45 | 25 | 30 | 45 | 25 | 30 | 45 | |||||||||
2500 | 25 | 30 | 45 | 25 | 30 | 45 | ||||||||||||
3000 | 30 | 45 | 60 | 30 | 45 | 60 | ||||||||||||
4000 | 30 | 45 | 60 | |||||||||||||||
5000 | 30 | 45 | 60 |
TA30P | TA60P | TA80P | |||||||
---|---|---|---|---|---|---|---|---|---|
Bus-bar | 30x20 | 60x30 | 80x50 | ||||||
Cable | Ø20 | Ø30 | Ø50 | ||||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | VA | ||||||
100 | 3 | ||||||||
150 | 3,75 | ||||||||
200 | 2,5 | 4 | |||||||
250 | 3,75 | 5 | 2,5 | 3,75 | 2,5 | 3,75 | |||
300 | 2,5 | 4 | 6 | 3,75 | 5 | 3,75 | 5 | ||
400 | 3,75 | 5 | 10 | 2,5 | 3,75 | 7,5 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 | 3,75 | 5 | 15 | |||
600 | 5 | 7,5 | 20 | 5 | 7,5 | 20 | |||
750 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | |||
800 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | |||
1000 | 10 | 15 | 20 | 10 | 15 | 20 |
TA100P | TA125P | TA160P | |||||||
---|---|---|---|---|---|---|---|---|---|
Bus-bar | 100x80 | 125x80 | 160x80 | ||||||
Cable | Ø80 | Ø80 | Ø80 | ||||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | VA | ||||||
250 | 2,5 | 3,75 | |||||||
300 | 3,75 | 5 | |||||||
400 | 2,5 | 3,75 | 7,5 | ||||||
500 | 3,75 | 5 | 15 | 5 | 7,5 | 2,5 | 3,75 | 7,5 | |
600 | 5 | 7,5 | 20 | 5 | 15 | 3,75 | 5 | 10 | |
750 | 7,5 | 10 | 20 | 5 | 10 | 20 | 5 | 10 | 20 |
800 | 7,5 | 10 | 20 | 7,5 | 10 | 20 | 7,5 | 10 | 20 |
1000 | 10 | 15 | 20 | 10 | 20 | 30 | 10 | 20 | 30 |
1200 | 15 | 20 | 30 | 15 | 20 | 30 | 15 | 20 | 30 |
1500 | 15 | 20 | 30 | 20 | 30 | 45 | 20 | 30 | 45 |
2000 | 20 | 30 | 45 | 25 | 30 | 45 | 25 | 30 | 45 |
2500 | 25 | 30 | 45 | 25 | 30 | 45 | |||
3000 | 30 | 45 | 60 | 30 | 45 | 60 | |||
4000 | 30 | 45 | 60 | ||||||
5000 | 30 | 45 | 60 |
TA30P | TA60P | |||||
---|---|---|---|---|---|---|
Bus-bar | 30x20 | 60x30 | ||||
Cable | Ø20 | Ø30 | ||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | ||||
100 | 3 | |||||
150 | 3,75 | |||||
200 | 2,5 | 4 | ||||
250 | 3,75 | 5 | 2,5 | 3,75 | ||
300 | 2,5 | 4 | 6 | 3,75 | 5 | |
400 | 3,75 | 5 | 10 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 | |||
600 | 5 | 7,5 | 20 | |||
750 | 7,5 | 10 | 20 | |||
800 | 7,5 | 10 | 20 | |||
1000 | 10 | 15 | 20 |
TA80P | TA100P | |||||
---|---|---|---|---|---|---|
Bus-bar | 80x50 | 100x80 | ||||
Cable | Ø50 | Ø80 | ||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | ||||
250 | 2,5 | 3,75 | 2,5 | 3,75 | ||
300 | 3,75 | 5 | 3,75 | 5 | ||
400 | 2,5 | 3,75 | 7,5 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 | 3,75 | 5 | 15 |
600 | 5 | 7,5 | 20 | 5 | 7,5 | 20 |
750 | 7,5 | 10 | 20 | 7,5 | 10 | 20 |
800 | 7,5 | 10 | 20 | 7,5 | 10 | 20 |
1000 | 10 | 15 | 20 | 10 | 15 | 20 |
1200 | 15 | 20 | 30 | |||
1500 | 15 | 20 | 30 | |||
2000 | 20 | 30 | 45 |
TA125P | TA160P | |||||
---|---|---|---|---|---|---|
Bus-bar | 125x80 | 160x80 | ||||
Cable | Ø80 | Ø80 | ||||
Accuracy class | 0,5 | 1 | 3 | 0,5 | 1 | 3 |
Ipn (A) | VA | VA | ||||
500 | 5 | 7,5 | 2,5 | 3,75 | 7,5 | |
600 | 5 | 15 | 3,75 | 5 | 10 | |
750 | 5 | 10 | 20 | 5 | 10 | 20 |
800 | 7,5 | 10 | 20 | 7,5 | 10 | 20 |
1000 | 10 | 20 | 30 | 10 | 20 | 30 |
1200 | 15 | 20 | 30 | 15 | 20 | 30 |
1500 | 20 | 30 | 45 | 20 | 30 | 45 |
2000 | 25 | 30 | 45 | 25 | 30 | 45 |
2500 | 25 | 30 | 45 | 25 | 30 | 45 |
3000 | 30 | 45 | 60 | 30 | 45 | 60 |
4000 | 30 | 45 | 60 | |||
5000 | 30 | 45 | 60 |
TA30P | |||
---|---|---|---|
Bus-bar | 30x20 | ||
Cable | Ø20 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
100 | 3 | ||
150 | 3,75 | ||
200 | 2,5 | 4 | |
250 | 3,75 | 5 | |
300 | 2,5 | 4 | 6 |
400 | 3,75 | 5 | 10 |
TA60P | |||
---|---|---|---|
Bus-bar | 60x30 | ||
Cable | Ø30 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
250 | 2,5 | 3,75 | |
300 | 3,75 | 5 | |
400 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 |
600 | 5 | 7,5 | 20 |
750 | 7,5 | 10 | 20 |
800 | 7,5 | 10 | 20 |
1000 | 10 | 15 | 20 |
TA80P | |||
---|---|---|---|
Bus-bar | 80x50 | ||
Cable | Ø50 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
250 | 2,5 | 3,75 | |
300 | 3,75 | 5 | |
400 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 |
600 | 5 | 7,5 | 20 |
750 | 7,5 | 10 | 20 |
800 | 7,5 | 10 | 20 |
1000 | 10 | 15 | 20 |
TA100P | |||
---|---|---|---|
Bus-bar | 100x80 | ||
Cable | Ø80 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
250 | 2,5 | 3,75 | |
300 | 3,75 | 5 | |
400 | 2,5 | 3,75 | 7,5 |
500 | 3,75 | 5 | 15 |
600 | 5 | 7,5 | 20 |
750 | 7,5 | 10 | 20 |
800 | 7,5 | 10 | 20 |
1000 | 10 | 15 | 20 |
1200 | 15 | 20 | 30 |
1500 | 15 | 20 | 30 |
2000 | 20 | 30 | 45 |
TA125P | |||
---|---|---|---|
Bus-bar | 125x80 | ||
Cable | Ø80 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
500 | 5 | 7,5 | |
600 | 5 | 15 | |
750 | 5 | 10 | 20 |
800 | 7,5 | 10 | 20 |
1000 | 10 | 20 | 30 |
1200 | 15 | 20 | 30 |
1500 | 20 | 30 | 45 |
2000 | 25 | 30 | 45 |
2500 | 25 | 30 | 45 |
3000 | 30 | 45 | 60 |
TA160P | |||
---|---|---|---|
Bus-bar | 160x80 | ||
Cable | Ø80 | ||
Accuracy class | 0,5 | 1 | 3 |
Ipn (A) | VA | ||
500 | 2,5 | 3,75 | 7,5 |
600 | 3,75 | 5 | 10 |
750 | 5 | 10 | 20 |
800 | 7,5 | 10 | 20 |
1000 | 10 | 20 | 30 |
1200 | 15 | 20 | 30 |
1500 | 20 | 30 | 45 |
2000 | 25 | 30 | 45 |
2500 | 25 | 30 | 45 |
3000 | 30 | 45 | 60 |
4000 | 30 | 45 | 60 |
5000 | 30 | 45 | 60 |
Dimensions and mounting dimensions of TAxP series transformers

A | B | C | D | |
---|---|---|---|---|
TA30P | 32 | 22 | 106 | 90 |
TA60P | 62 | 32 | 136 | 100 |
TA80P | 82 | 52 | 156 | 120 |
TA100P | 104 | 82 | 178 | 150 |
TA120P | 127 | 82 | 201 | 150 |
TA160P | 162 | 82 | 236 | 150 |
Delivery terms according to company's process:
from 3 days
if in stock
from 5 days
if in stock
from 30 days
if out of stock